Analog differential trigger

Short description

The output is set and reset depending on a configurable threshold and a differential value.

Connection

Description

Input Ax

Input Ax is one of the following analog signals:

  • AI1 to AI8 (*)

  • AM1to AM6 (if 0BA6) or AM1 to AM16 (if 0BA7)

  • AN1...AN32 (if 0BA7)

  • AQ1 and AQ2

  • SAQ1...SAQ16 (if 0BA7).

  • The block number of a function with analog output

Parameter

A: Gain

Range of values: ±10.00

B: Zero offset
Range of values: ±10,000

On: On/Off threshold
Range of values: ±20,000

Δ: Differential value for calculating the off parameter
Range of values: ±20,000

p: Number of decimals
Range of values: 0, 1, 2, 3

Output Q

Q is set or reset, depending on the threshold and difference values.

* AI1 to AI8: 0 to 10 V corresponds with 0 to 1000 (internal value).

A: Gain

Range of values: 0.00 to 10.00

Parameter p (number of decimals)

Parameter p applies only to the display of On, Off and Ax values in a message text.

Parameter p does not apply to the comparison of On and Off values. (The compare function ignores the decimal point.)

Timing diagram A: Function with negative difference Delta

Timing diagram B: Function with positive difference Delta

Description of the function

The function fetches the analog signal at input Ax.

Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) is added to product, i.e.

(Ax * gain) + offset = actual value of Ax.

Output Q is set or reset, depending on the set (On) threshold and difference value (Delta). The function automatically calculates the Off parameter: Off = On + Delta, whereby Delta may be positive or negative. See the calculation rule below.

Calculation rule

Particular characteristics to be noted when configuring

Refer to the help on analog block parameters in the Information on analog value processing section.

Special Functions Overview